InteliDrive DCU Marine - 3.0.0 Global Guide
181
Related FW 3.0.0 Related applications All
Comm object 156
Description
External āedge sensitiveā request for engine start. Binary input is active in all AUX, EME, HRB and PRP
modes and inactive in LOC (Local) mode. There is only one start attempt, use RemRepStart (PRP) binary
input or Blackout Start (AUX, EME and HRB) binary input for repetitive starting procedure using Cranking
Attempts and CrankFail Pause setpoints until the engine does not start. Unsuccessful start is recorded to
Alarm list and History. The second edge on Binary input Remote Start skips the Idle time when engine is
running in Idle state.
Binary input Remote Start signal is equivalent to ID-DCU MARINE front panel Start button.
Remote Start
6 back to List of LBI
Related FW 3.0.0 Related applications All
Comm object 157
Description
Engine āedge sensitiveā stop request. The first edge changes engine state from running to cooling, the
second edge stops engine (skip the rest of cooling). Binary input is inactive in LOC (Local) mode.
Remote Stop signal is equivalent to ID-DCU MARINE front panel Stop button.
Note: Binary inputs Remote Start and Remote Stop are edge (not level) sensitive. Minimal pulse
duration to safely detect the edge is at least the 120 ms (binary input sampling rate is 100 ms).
Remote Stop
6 back to List of LBI
Related FW 3.0.0 Related applications All
Comm object 837
Description
Active signal inhibits automatic DPF filter regeneration.
Reg Inhib
6 back to List of LBI
Related FW 3.0.0 Related applications All
Comm object 836
Description
Active signal inhibits automatic DPF filter regeneration.
RegenForce
6 back to List of LBI