Configuration
7-9
L
EDSVS9332P-D21 EN 3.0
Establish connections
1. Determine the signal source for ARIT2-IN1:
– Change to the code level using the arrow keys
– Select C0601/1 using B or A.
– Change to the parameter level using PRG.
– Select output AIN2-OUT (selection number 55) using B or A.
– Confirm using SH + PRG
– Change to the code level again using PRG.
2. Determine signal source for ARIT2-IN2:
– Select C0601/2 using B.
– Change to the parameter level using PRG.
– Select output AIN2-OUT (selection number 55) using B or A.
– Confirm using SH + PRG
– Change to the code level again using PRG.
3. Parameterise ARIT2:
– Select C0600 using A.
– Change to the parameter level using PRG.
– Select multiplication (selection number 3).
– Confirm using SH + PRG
– Change to the code level again using PRG.
4. Determine signal source for AOUT1:
– Select C0431 using A.
– Change to the parameter level using PRG.
– Select output ARIT2-OUT (selection number 5505).
– Confirm using SH + PRG
– Change to the code level again using PRG.
5. Enter function block ARIT2 in the processing table:
– Select C0465 and subcode 8 using B.
– Change to the parameter level using PRG.
– Enter function block ARIT2 (selection number 5505).
– Confirm using SH + PRG
– Change to the code level again using PRG.
– The sequence of the FB processing is thus determined.