3.3.4 Fuses and cable cross-sections
Type
Mains input L1, L2, L3, PE/Motor connection U, V, W Input +UG, -UG
y
p
Operation without mains filter Operation with mains filter
Fuse E.l.c.b. Cable cross-section
2)
Fuse E.l.c.b. Cable
cross-section
2)
Fuse Cable
cross-section
2)
VDE UL VDE mm
2
AWG VDE UL VDE mm
2
AWG mm
2
AWG
9321 M6A 5A B6A 1 17 M6A 5A B6A 1 17 6A 1 18
9322 M6A 5A B6A 1 17 M6A 5A B6A 1 17 6A 1 18
9323 M 10A 10A B 10A 1.5 15 M 10A 10A B 10A 1.5 15 12A 1.5 14
9324 - - - - - M 10A 10A B 10A 1.5 15 12A 1.5 14
9325 M 32A 25A B 32A j6 9 M 20A 20A B 20A 4 11 20A 4 12
9326 - - - - - M 32A 25A B 32A j6 9 40A 10 8
9327 M 63A 63A - 16 j6 35A 35A - 10 7 80A 25 3
9328 - - - - - 50A 50A - 16 5 80A 25 3
9329 - - - - - 80A 80A - 25 3 100A 50 1
9330 - - - - - 100A 100A - 50 0 2 * 80A
1)
2*25 2*3
9331 - - - - - 125A 125 A - 70 2/0 2 * 100A
1)
2*50 2*1
9332 - - - - - 160A 175 A - 95 3/0 3 * 80A
1)
3*25 3*3
1)
The DC bus fuses are connected in parallel
2)
The valid local regulations must be observed
For operation of the controllers in a UL-approved plant:
Use only UL-approved fuses and fuse holders:
500 V to 600 V in the mains input (AC)
700VintheDCbus(DC).
Tripping characteristic H or K5.
Use only UL-approved cables.
Tip!
UL-approved fuses and fuse holders can be obtained from e.g. Bussmann or Ferraz.
Connection of the motor cables
The protection of the motor cables is not necessary for functional reasons.
ThedatainthetableOperation with mains filters are applicable.