Technical data
3-6
L
EDSVS9332P-B EN 3.0
3.3.4 Fuses and cable cross-sections
Type
Mains input L1, L2, L3, PE/Motor connection U, V, W Input +UG, -UG
Operation without mains filter Operation with mains filter
Fuse E.l.c.b. Cable cross-section
2)
Fuse E.l.c.b. Cable
cross-section
2)
Fuse Cable
cross-section
2)
VDE UL VDE mm
2
AWG VDE UL VDE mm
2
AWG mm
2
AWG
9321 M6A 5A B6A 1 17 M6A 5A B6A 1 17 6A 1 18
9322 M6A 5A B6A 1 17 M6A 5A B6A 1 17 6A 1 18
9323 M 10A 10A B 10A 1.5 15 M 10A 10A B 10A 1.5 15 12A 1.5 14
9324 - - - - - M 10A 10A B 10A 1.5 15 12A 1.5 14
9325 M 32A 25A B 32A j6 9 M 20A 20A B 20A 4 11 20A 4 12
9326 - - - - - M 32A 25A B 32A j6 9 40A 10 8
9327 M 63A 63A - 16 j6 35A 35A - 10 7 80A 25 3
9328 - - - - - 50A 50A - 16 5 80A 25 3
9329 - - - - - 80A 80A - 25 3 100A 50 1
9330 - - - - - 100A 100A - 50 0 2 * 80A
1)
2*25 2*3
9331 - - - - - 125A 125 A - 70 2/0 2 * 100A
1)
2*50 2*1
9332 - - - - - 160A 175 A - 95 3/0 3 * 80A
1)
3*25 3*3
1)
The DC bus fuses are connected in parallel
2)
The valid local regulations must be observed
For operation of the controllers in a UL-approved plant:
•
Use only UL-approved fuses and fuse holders:
– 500 V to 600 V in the mains input (AC)
– 700VintheDCbus(DC).
– Tripping characteristic ”H” or ”K5”.
•
Use only UL-approved cables.
Tip!
UL-approved fuses and fuse holders can be obtained from e.g. Bussmann or Ferraz.
Connection of the motor cables
•
The protection of the motor cables is not necessary for functional reasons.
•
Thedatainthetable”Operation with mains filters” are applicable.