Max. permissible cable cross-sections and screw tightening torques:
Type Max. permissible
Screw-tightening torques
y
p
p
cable cross-sections
L1, L2, L3, +UG, -UG PE connection
9321 ... 9326 4mm
2
0.5 ... 0.6 Nm (4.4 ... 5.3 lb-in) 3.4 Nm (30 lb-in)
9327 ... 9329 25 mm
2
5 Nm (44 lb-in)
9330 ... 9331 95 mm
2
15 Nm (132 lb-in)
9332 120 mm
2
30 Nm (264 lb-in)
Cable cross-sections Connection with Note
Up to 4 mm
2
Wire end ferrules
Up to 6 mm
2
Pin-end connectors
>25 mm
2
Ring cable lugs The cable cross-section is only limited by the cable bushing in the housing.
Fuses
Fuses and cable cross-sections The specific ations in chapter 3.3.4 are recommendations and refer to
the use in control cabinets and machines
installation in cable ducts,
max. ambient temperature of +40 °C.
Selection of the cable cross-section Please consider the voltage drop under load (according to DIN 18015, part 1: 3%).
Cable and controller protection on the AC side
(L1, L2, L3)
By means of standard commercial fuses.
By means o f fuses in UL-conform plants must have UL approval.
The rated voltages of the fuses must be di mensioned according to the mains
voltage at the site. The activation characteristic is defined with ”H” or ”K5”.
Cable and controller protection on the DC side
(+UG, -UG)
By means o f recommended DC fuses.
The fuses/fuse holders recommended by Lenze are UL a pproved.
For DC group drives or supply using a DC source: Please observe the notes in part F of the systems manual.
Connection of a brake unit When connecting the brake unit to terminals +UG / -UG, please note that the fuses
and cross sections indicated in chapter 3.3.4 do not apply to the brake unit. These
unit-specific data can be obtained from the technical documentation for the brake
unit.
Further information For the protection of cables and the controller please see the c hapter ”Accessories” in
the “Planning” folder.
Other standards The compliance with other standards (e.g.: VDE 0113, VDE 0289, etc.) remains the