Installation
4-17
L
EDSVS9332P-B EN 3.0
Types 9327 ... 9329
Stop!
Do not use clips for strain relief.
9300STD030
PE
T1
T2
U
VW
4
1
0
2
3
Fig. 4-10 Proposal for motor connection
PE threaded bolt
Fasten shield sheet with two M4 screws.
Clamp motor cable shield and cable shield for motor temperature monitoring with clip.
The shielding of the motor cable is only required to comply with existing standards (e. g. VDE 0160, EN50178, EN61800-3).
Connect motor cable to threaded bolts U, V, W.
Observe c orrect pole co nnection and maximum motor cabl e length.
Connect cable for motor temperature monitoring to screw terminals T1 and T2.
Tip!
For an improved shield connection, additionally connect the shield to the PE threaded bolt.