Installation
4-21
L
EDSVS9332P-B EN 3.0
4.2.7.3 Connection of a brake unit
•
When connecting a brake unit (brake module with internal brake resistor or brake chopper
with external brake resistor) observe the corresponding Operating Instructions in all cases.
Stop!
•
Design the circuit so that, if the temperature monitoring of the brake unit is activated,
– the controllers are inhibited (X5/28 = LOW).
– the mains is disconnected.
•
Examples:
– Chapter 4.3, “Installation of a CE-typical drive system”.
(E 4-41)
– Fig. 4-13, “Decentralized supply for DC-bus connection of several drives”.
(E 4-22)