FX Series PLC User's Manual - Data Communication Edition
N:N Network
6 Test Run (Communication Test)
6.1 Test Procedure
A
Common Items
B
N:N Network
C
Parallel Link
D
Computer Link
E
Inverter
Communication
F
Non-Protocol
Communication
(RS/RS2 Instruction)
G
Non-Protocol
Communication
(FX
2N
-232IF)
H
Programming
Communication
I
Remote
Maintenance
Apx.
Discontinued
models
6 Confirming the link of slave stations
Set the PLC inputs (X000 to X003) to ON or OFF in each slave station, and confirm that the outputs
(Y004 to Y007, Y010 to Y013, Y014 to Y017... Y030 to Y033) turn ON or OFF in each slave station.
→ If unable to establish link, refer to "Chapter 9. Troubleshooting."
Assignment of inputs and outputs (link devices)
The table below shows devices used in the test programs shown later:
Station No. Input (X) Link device Output (Y)
0 Master station X000 to X003 D0 Y000 to Y003
1 Slave station No. 1 X000 to X003 D10 Y004 to Y007
2 Slave station No. 2 X000 to X003 D20 Y010 to Y013
3 Slave station No. 3 X000 to X003 D30 Y014 to Y017
4 Slave station No. 4 X000 to X003 D40 Y020 to Y023
5 Slave station No. 5 X000 to X003 D50 Y024 to Y027
6 Slave station No. 6 X000 to X003 D60 Y030 to Y033
7 Slave station No. 7 X000 to X003 D70 Y034 to Y037
Set the inputs X000 to
X003 to ON or OFF.
Master station
Slave station No. 1
Confirm that the inputs (X000 to
X003) in the slave station No. 2
turn ON or OFF according to the
outputs (Y010 to Y013)
respectively.
Set the inputs X000 to
X003 to ON or OFF.
Slave station No. 2
Confirm that the inputs (X000 to
X003) in the slave station No. 1
turn ON or OFF according to the
outputs (Y004 to Y007)
respectively.
Confirm that the inputs (X000 to
X003) in the slave station No. 2
turn ON or OFF according to the
outputs (Y010 to Y013)
respectively.
Confirm that the inputs (X000 to
X003) in the slave station No. 1
turn ON or OFF according to the
outputs (Y004 to Y007)
respectively.


 