7.3 Cautions on Program Creation
1. Program for reading link devices
1) Do not change the contents of link devices for the other station.
2) When a link error occurs, the link device information remains the same as the status just before the error.
Create a fail-safe program which does not cause abnormality even if a link error occurs.
2. Cautions on using FX3U/FX3UC PLCs
1) Only ch1 or ch2 can be set in the parallel link.
2) Do not use the N:N Network and the parallel link at the same time.
(For example, it is not allowed to use ch1 for the N:N Network and simultaneously use ch2 for the parallel
link.)