FX Series PLC User's Manual - Data Communication Edition
Computer Link
7 Commands
7.2 WR Command [Reads Device Memory in 1-Word Units]
Important point
The WR command handles data in 1-word units. When reading thirty-two devices from X040 to X077, specify
the number of device points as "02" (One point specifies 16 devices.)
Example 2: When reading the present value of two devices from T123 and T124 in the PLC whose station
number is 5 (while the message waiting time is set to 0 ms)
A
C
K
0 5 F F
E
T
X
B 3
S
T
X
0 5 F F
7 B C 9 1 2 3 4
0 2 6 4
E
N
Q
0 5 F F W R 0
This range is regarded as the
sum check target.
This range is regarded as the
sum check target.
35
H
30
H
46
H
46
H
52
H
57
H
30
H
54
H
33
H
32
H
31
H
4E
H
32
H
30
H
34
H
36
H
05
H
35
H
30
H
46
H
46
H
02
H
33
H
42
H
03
H
35
H
30
H
46
H
46
H
06
H
37
H
39
H
43
H
42
H
31
H
34
H
33
H
32
H
Indicates that the current value of T123 is "7BC9H
(hexadecimal) (which is "31689" in decimal).
Indicates that the current value of T124 is "1234H
(hexadecimal) (which is "4660" in decimal).