E-34
FX Series PLC User's Manual - Data Communication Edition
Inverter Communication
5 Communication Setting in Inverter
5.3 E500 Series (When Connected to PU Port)
• Method to set each digit of the parameter number
a) Press the SET key to flash the most significant digit. Set a numeric value using the UP and DOWN
keys.
b) Press the SET key to flash the middle digit. Set a numeric value using the UP and DOWN keys.
c) Press the SET key to flash the least significant digit. Set a numeric value using the UP and DOWN
keys.
4 Setting the set value of Pr. 118 to "192"
("192" indicates the baud rate of 19200 bps.)
1. Press the SET key to read the currently set value. Change the set value using the UP and
DOWN keys.
2. Press and hold the SET key for 1.5 seconds to set "192".
3. Press the SET key to display the next parameter.
5 Change other parameters in the same way as step 3.
→ For details on parameters to be set, refer to Subsection 5.3.1.
The set value and parameter number are displayed
alternately.
Press and hold it
for 1.5 sec.
The parameter number and set value are displayed
alternately