11.10 H: Terminal Functions
532 YASKAWA SIEPC71061705H GA700 Series Technical Manual
H2-xx: MFDO Setting Values
Setting Value Function Description Ref.
0 During Run
The terminal activates when you input a Run command and when the drive is outputting voltage.
ON : Drive is running
OFF : Drive is stopping
830
1 Zero Speed
The terminal activates when the output frequency < E1-09 [Minimum Output Frequency] or b2-01 [DC Injection/
Zero SpeedThreshold].
Note:
Parameter A1-02 [Control Method Selection] selects which parameter is the reference.
A1-02 Setting Control method selection Parameter Used as the Reference
0 V/f E1-09
1 CL-V/f E1-09
2 OLV b2-01
3 CLV E1-09
4 AOLV E1-09
5 OLV/PM E1-09
6 AOLV/PM E1-09
7 CLV/PM b2-01
8 EZOLV E1-09
ON : Output frequency < value of E1-09 or b2-01.
OFF : Output frequency value of E1-09 or b2-01.
831
2 Speed Agree 1
The terminal turns on when the output frequency is in the range of the frequency reference ± L4-02 [Speed Agree
Detection Width].
Note:
The detection function operates in the two motor rotation directions.
The drive outputs the motor speed status when A1-02 = 3, 7 [CLV, CLV/PM]. It also outputs the motor speed
status when A1-02 = 4 and n4-72 = 1.
ON : The output frequency is in the range of frequency reference ± L4-02.
OFF : The output frequency does not align with the frequency reference although the drive is running.
831
3 User-Set Speed Agree 1
The terminal activates when the output frequency is in the range of L4-01 [Speed Agree Detection Level] ± L4-02
[Speed Agree Detection Width] and in the range of the frequency reference ± L4-02.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
The drive outputs the motor speed status when A1-02 = 3, 7 [CLV, CLV/PM]. It also outputs the motor speed
status when A1-02 = 4 and n4-72 = 1.
ON : The output frequency is in the range of L4-01 ± L4-02 and the range of frequency reference ± L4-02.
OFF : The output frequency is not in the range of L4-01 ± L4-02 or the range of frequency reference ± L4-02.
832
4 Frequency Detection 1
The terminal deactivates when the output frequency > L4-01 [Speed Agree Detection Level] + L4-02 [Speed
Agree Detection Width]. After the terminal deactivates, the terminal stays deactivated until the output frequency is
at the value of L4-01.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
The drive outputs the motor speed status when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM]. It
also outputs the motor speed status when A1-02 = 4 [AOLV] and n4-72 = 1 [Speed Feedback Mode = With
Encoder].
ON : The output frequency < L4-01, or the output frequency L4-01 + L4-02
OFF : The output frequency > L4-01 + L4-02
832
5 Frequency Detection 2
The terminal activates when the output frequency > L4-01 [Speed Agree Detection Level]. After the terminal
activates, the terminal stays activated until the output frequency is at the value of L4-01 - L4-02.
Note:
The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
The drive outputs the motor speed status when A1-02 = 3, 7 [Control Method Selection = CLV, CLV/PM]. It
also outputs the motor speed status when A1-02 = 4 [AOLV] and n4-72 = 1 [Speed Feedback Mode = With
Encoder].
ON : The output frequency > L4-01
OFF : The output frequency < L4-01 - L4-02, or the output frequency L4-01
833
6 Drive Ready
The terminal activates when the drive is ready and running.
833
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV
V/f
CL-V/f
OLV
CLV
AOLV
OLV/PM OLV/PM
AOLV/PM
CLV/PM
EZOLV