Setting Value Function Description Ref.
103 !User-Set Speed Agree 1
The terminal deactivates when the output frequency is in the range of L4-01 [Speed Agree Detection Level] ± L4-
02 [Speed Agree Detection Width] and in the range of the frequency reference ± L4-02.
Note:
• The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
• When using Closed Loop Vector Control, this is the value of “Motor Speed ± L4-02.”
ON : The output frequency is not in the range of “L4-01 ± L4-02” nor the range of frequency reference ± L4-02.
OFF : The output frequency is in the range of “L4-01 ± L4-02” and the range of frequency reference ± L4-02.
844
104 !Frequency Detection 1
The terminal deactivates when the output frequency is higher than the value of L4-01 [Speed Agree Detection
Level] + L4-02 [Speed Agree Detection Width]. When the terminal activates, it stays activated until the output
frequency = L4-01.
Note:
• The detection function operates in the two motor rotation directions. The drive uses the L4-01 value as the
forward/reverse detection level.
• In CLV, the motor speed is the reference.
ON : The output frequency is higher than L4-01 + L4-02.
OFF : The output frequency is less than L4-01 or is not more than L4-01 + L4-02.
844
105 !Frequency Detection 2
The terminal deactivates when the output frequency is higher than the value of L4-01 [Speed Agree Detection
Level]. When the terminal deactivates, it stays deactivated until the output frequency = L4-01 - L4-02.
ON : The output frequency is less than “L4-01 - L4-02,” or it is not more than L4-01.
OFF : The output frequency is more than L4-01.
844
106 !Drive Ready
The terminal deactivates when the drive is ready and running.
844
107 !DC Bus Undervoltage
The terminal deactivates when the DC bus voltage or control circuit power supply is at or below the voltage set in
L2-05 [Undervoltage Detection Lvl (Uv1)]. The terminal also deactivates when there is a fault with the DC bus
voltage.
ON : The DC bus voltage is more than the setting value of L2-05.
OFF : The DC bus voltage is less than the setting value of L2-05.
844
108 During Baseblock (N.C.)
The terminal deactivates during baseblock. When the drive is in baseblock, the drive output transistor stops
switching and does not make DC bus voltage.
ON : The drive is not in baseblock.
OFF : During baseblock
844
109 !Frequency Reference
from Keypad
Shows the selected frequency reference source.
ON : b1-01 [Frequency Reference Selection 1] or b1-15 [Frequency Reference Selection 2] is the frequency
reference source.
OFF : The keypad is the frequency reference source.
844
10A !Run Command from
Keypad
Shows the selected Run command source.
ON : b1-02 [Run Command Selection 1] or b1-16 [Run Command Selection 2] is the Run command source.
OFF : The keypad is the Run command source.
844
10B Torque Detection 1 (N.
C.)
The terminal deactivates when the drive detects overtorque or undertorque.
OFF : The output current/torque exceeds the torque value set with L6-02 [Torque Detection Level 1], or the level
has dropped and remained in this state longer than the time set with L6-03 [Torque Detection Time 1].
844
10C !Frequency Reference
Loss
The terminal deactivates when the drive detects a loss of frequency reference.
844
10D !Braking Resistor Fault
The terminal deactivates when the mounting-type braking resistor is overheating or when there is a braking
transistor fault.
844
10E !Fault
The terminal deactivates when the drive detects a fault.
Note:
Faults CPF00 and CPF01 [Control Circuit Error] are excluded.
844
110 !Alarm
The terminal deactivates when the drive detects a minor fault.
844
111 !Fault Reset Command
Active
The terminal deactivates when the drive receives the Reset command from the control circuit terminal, serial
communications, or the communication option.
844
112 !Timer Output
Sets the terminal as the timer output. Use this setting with the timer input set in H1-xx = 118 [MFDI Function
Selection = !Timer Function].
844