11.18 Parameters that Change from the Default Settings with A1-02 [Control Method Selection]
594 YASKAWA SIEPC71061705H GA700 Series Technical Manual
No. Name Range Unit
Control Method (A1-02 Setting)
V/f
(0)
CL-V/f
(1)
OLV
(2)
CLV
(3)
AOLV
(4)
L4-04
Speed Agree
Detection Width
(+/-)
0.0 - 20.0 0.1 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz 2.0 Hz
L8-38
Carrier
Frequency
Reduction
0 - 2 1
*3 *3 *3 *3
-
L8-40
Carrier Freq
Reduction Off-
Delay
0.00 - 2.00 0.01 s 0.50 0.50 0.50 0.50 -
L8-90
STPo Detection
Level (Low
Speed)
0 - 5000 1 - - - - -
n1-15
PWM Voltage
Offset
Calibration
0 - 2 1 1 1 1 1 2
n5-04
Speed Response
Frequency
0.00 - 500.00 0.01 Hz - - - 50.00 50.00
n8-35
Initial Pole
Detection
Method
0 - 2 1 - - - - -
n8-51
Pull-in Current
@ Acceleration
0 - 200 1% - - - - -
o1-03
Frequency
Display Unit
Selection
0 - 3 1 0 0 0 0 0
o1-04
V/f Pattern
Display Unit
0 - 1 1 - - - 0 0
*1 The default setting changes when the setting for o2-04 [Drive Model Selection] changes.
*2 Models 2211 to 2415 and 4103 to 4675 use these default settings when C6-01 = 1 [Normal / Heavy Duty Selection = Normal Duty
Rating]. Models 2257 to 2415 and 4140 to 4675 use these default settings when C6-01 = 0 [Heavy Duty Rating].
A1-02 = 2 [Open Loop Vector]: 2.00
A1-02 = 3, 4 [Closed Loop Vector, Advanced Open Loop Vector]: 0.05
*3 The default setting changes when C6-01 [Normal / Heavy Duty Selection] changes.
*4 The maximum value changes when A1-02 changes:
When A1-02 = 0, 2 [V/f Control, Open Loop Vector], the maximum value is 590.0 Hz.
When A1-02 = 1, 3 [V/f Control with Encoder, Closed Loop Vector], the maximum value is 400.0 Hz.
When A1-02 = 4 [Advanced Open Loop Vector], the maximum value is 120.0 Hz.
*5 The default setting changes when the drive model and E1-03 [V/f Pattern Selection] change.
*6 This is the value for 200 V class drives. Double the value for 400 V class drives.
*7 The maximum value changes when A1-02 changes:
When A1-02 = 0, 2 [V/f Control, Open Loop Vector], the maximum value is 590.0 Hz.
When A1-02 = 1 [V/f Control with Encoder], the maximum value is 400.0 Hz.
When A1-02 = 4 [Advanced Open Loop Vector], the maximum value is 120.0 Hz.
*8 The minimum value changes when A1-02 changes:
When A1-02 = 0, 2 [V/f Control, Open Loop Vector], the minimum value is -590.0 Hz.
When A1-02 = 1, 3 [V/f Control with Encoder, Closed Loop Vector], the minimum value is -400.0 Hz.
When A1-02 = 4 [Advanced Open Loop Vector], the minimum value is -120.0 Hz.
A1-02 = 5 to 8 [Control Method for PM Motors and EZ Vector Control]
No. Name Range Unit
Control Method (A1-02 Setting)
OLV/PM
(5)
AOLV/PM
(6)
CLV/PM
(7)
EZOLV
(8)
b2-01
DC Injection/Zero
SpeedThreshold
0.0 - 10.0 0.1 0.5 Hz 1.0% 0.5% 0.5 Hz
b2-04
DC Inject Braking
Time at Stop
0.00 - 10.00 0.01 s 0.00 0.00 0.00 0.00
b3-01
Speed Search at Start
Selection
0 - 1 1 0 0 - 0
b3-02
SpeedSearch
Deactivation Current
0 - 200 1% - - - -
b3-08
Speed Estimation ACR
P Gain
0.00 - 6.00 0.01 0.30 0.30 - 0.60
*1