Parameter List
11
11.21 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA SIEPC71061705H GA700 Series Technical Manual 607
No.
*1
Name Unit Default
- Drive Model - 2110 2138 2169 2211
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 70 72 73 74
E2-11
(E4-11)
Motor Rated
Power
kW 22 30 30 37 37 45 45 55
L2-02
Power Loss
Ride Through
Time
s 2 2 2 2 2 2 2 2
L2-03
Minimum
Baseblock
Time
s 1 1.1 1.1 1.1 1.1 1.2 1.2 1.3
L2-04
Powerloss V/f
Recovery
Ramp Time
s 0.6 0.6 0.6 0.6 0.6 1 1 1
L2-05
Undervoltage
Detection Lvl
(Uv1)
- 190 190 190 190 190 190 190 190
L3-24
Motor Accel
Time @ Rated
Torque
s 0.355 0.323 0.323 0.32 0.32 0.387 0.387 0.317
L8-02
Overheat
Alarm Level
°C 105 105 115 115 105 105 105 105
L8-09
Output
Ground Fault
Detection
- 1 1 1 1 1 1 1 1
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 2 2 2 2 2 2 2 2
n1-03
Hunting
Prevention
Time Constant
ms 10 10 10 10 10 10 10 10
n1-16
Hunting
Prevention
High Fc Gain
- 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
n5-02
Motor Inertia
Acceleration
Time
s 0.355 0.323 0.323 0.32 0.32 0.387 0.387 0.317
*1 Parameters within parentheses are for motor 2.
No.
*1
Name Unit Default
- Drive Model - 2257 2313 2360 2415
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 75 76 77 78
E2-11
(E4-11)
Motor Rated
Power
kW 55 75 75 90 90 110 110 110
b3-04
V/f Gain
during Speed
Search
% 80 80 80 80 80 80 80 80
b3-06
Speed
Estimation
Current Level
1
- 0.5 0.7 0.7 0.7 0.7 0.7 0.7 0.7
b3-08
Speed
Estimation
ACR P Gain
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-26
Direction
Determination
Level
- 1000 1000 1000 1000 1000 1000 1000 1000
b8-03
Energy Saving
Filter Time