11.21 Defaults by Drive Model and Duty Rating ND/HD
608 YASKAWA SIEPC71061705H GA700 Series Technical Manual
No.
*1
Name Unit Default
- Drive Model - 2257 2313 2360 2415
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 75 76 77 78
E2-11
(E4-11)
Motor Rated
Power
kW 55 75 75 90 90 110 110 110
b8-04
Energy Saving
Coefficient
Value
- 31.35 23.1 23.1 20.65 20.65 18.12 18.12 18.12
C5-17
(C5-37)
Motor Inertia kgm
2
0.49 0.90 0.90 1.10 1.10 1.90 1.90 1.90
C6-02
Carrier
Frequency
Selection
- 1 7 1 7 1 7 1 7
E2-01
(E4-01)
Motor Rated
Current (FLA)
A 190 260 260 260 260 260 260 260
E2-02
(E4-02)
Motor Rated
Slip
Hz 1.43 1.39 1.39 1.39 1.39 1.39 1.39 1.39
E2-03
(E4-03)
Motor No-
Load Current
A 45.6 72 72 72 72 72 72 72
E2-05
(E4-05)
Motor Line-
to-Line
Resistance
Ω 0.022 0.023 0.023 0.023 0.023 0.023 0.023 0.023
E2-06
(E4-06)
Motor
Leakage
Inductance
% 20.5 20 20 20 20 20 20 20
E2-10
(E4-10)
Motor Iron
Loss
W 960 1200 1200 1200 1200 1200 1200 1200
E5-01
PM Motor
Code
Selection
- 1215 1215 1216 1216 FFFF FFFF FFFF FFFF
L2-02
Power Loss
Ride Through
Time
s 2 2 2 2 2 2 2 2
L2-03
Minimum
Baseblock
Time
s 1.3 1.5 1.5 1.5 1.5 1.7 1.7 1.7
L2-04
Powerloss V/f
Recovery
Ramp Time
s 1 1 1 1 1 1 1 1
L2-05
Undervoltage
Detection Lvl
(Uv1)
- 190 190 190 190 190 190 190 190
L3-24
Motor Accel
Time @ Rated
Torque
s 0.317 0.533 0.533 0.592 0.592 0.646 0.646 0.646
L8-02
Overheat
Alarm Level
°C 105 105 105 105 105 105 105 105
L8-09
Output
Ground Fault
Detection
- 1 1 1 1 1 1 1 1
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 2 2 2 2 2 2 2 2
n1-03
Hunting
Prevention
Time Constant
ms 10 10 10 10 100 100 100 100
n1-16
Hunting
Prevention
High Fc Gain
- 0.50 0.50 0.50 0.50 1.00 1.00 1.00 1.00
n5-02
Motor Inertia
Acceleration
Time
s 0.317 0.533 0.533 0.592 0.592 0.646 0.646 0.646
*1 Parameters within parentheses are for motor 2.