11.21 Defaults by Drive Model and Duty Rating ND/HD
610 YASKAWA SIEPC71061705H GA700 Series Technical Manual
No.
*1
Name Unit Default
- Drive Model - 4002 4004 4005 4007
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 92 93 94 95
E2-11
(E4-11)
Motor Rated
Power
kW 0.4 0.75 1.1 1.5 1.5 2.2 2.2 3.0
L8-09
Output
Ground Fault
Detection
- 1 1 1 1 1 1 1 1
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 1 1 1 1 1 1 1 1
n1-03
Hunting
Prevention
Time Constant
ms 10 10 10 10 10 10 10 10
n1-16
Hunting
Prevention
High Fc Gain
- 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
n5-02
Motor Inertia
Acceleration
Time
s 0.178 0.142 0.142 0.166 0.166 0.145 0.145 0.145
*1 Parameters within parentheses are for motor 2.
No.
*1
Name Unit Default
- Drive Model - 4009 4012 4018 4023
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. 96 97 99 9A
E2-11
(E4-11)
Motor Rated
Power
kW 3.0 4.0 4.0 5.5 5.5 7.5 7.5 11
b3-04
V/f Gain
during Speed
Search
% 100 100 100 100 100 100 100 100
b3-06
Speed
Estimation
Current Level
1
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-08
Speed
Estimation
ACR P Gain
- 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
b3-26
Direction
Determination
Level
- 1000 1000 1000 1000 1000 1000 1000 1000
b8-03
Energy Saving
Filter Time
s 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
b8-04
Energy Saving
Coefficient
Value
- 265.7 245.8 245.8 189.5 189.5 145.38 145.38 140.88
C5-17
(C5-37)
Motor Inertia kgm
2
0.0158 0.0158 0.0158 0.0255 0.026 0.037 0.037 0.053
C6-02
Carrier
Frequency
Selection
- 1 7 1 7 1 7 1 7
E2-01
(E4-01)
Motor Rated
Current (FLA)
A 5.7 7 7 9.8 9.8 13.3 13.3 19.9
E2-02
(E4-02)
Motor Rated
Slip
Hz 2.7 2.7 2.7 1.5 1.5 1.3 1.3 1.7
E2-03
(E4-03)
Motor No-
Load Current
A 1.9 2.3 2.3 2.6 2.6 4 4 5.6