11.21 Defaults by Drive Model and Duty Rating ND/HD
614 YASKAWA SIEPC71061705H GA700 Series Technical Manual
No.
*1
Name Unit Default
- Drive Model - 4075 4089 4103 4140
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. A1 A2 A3 A4
E2-11
(E4-11)
Motor Rated
Power
kW 30 37 37 45 45 55 55 75
E2-06
(E4-06)
Motor
Leakage
Inductance
% 20.7 18.8 18.8 19.9 19.9 20 20 20
E2-10
(E4-10)
Motor Iron
Loss
W 750 925 925 1125 1125 1260 1260 1600
E5-01
PM Motor
Code
Selection
- 1242 1242 1243 1243 1244 1244 1245 1245
L2-02
Power Loss
Ride Through
Time
s 2 2 2 2 2 2 2 2
L2-03
Minimum
Baseblock
Time
s 1.1 1.1 1.1 1.2 1.2 1.2 1.2 1.3
L2-04
Powerloss V/f
Recovery
Ramp Time
s 0.6 0.6 0.6 0.6 0.6 1 1 1
L2-05
Undervoltage
Detection Lvl
(Uv1)
- 380 380 380 380 380 380 380 380
L3-24
Motor Accel
Time @ Rated
Torque
s 0.323 0.32 0.32 0.387 0.387 0.317 0.317 0.533
L8-02
Overheat
Alarm Level
°C 120 120 115 115 126 120 120 120
L8-09
Output
Ground Fault
Detection
- 1 1 1 1 1 1 1 1
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 2 2 2 2 2 2 2 2
n1-03
Hunting
Prevention
Time Constant
ms 10 10 10 10 10 10 30 30
n1-16
Hunting
Prevention
High Fc Gain
- 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
n5-02
Motor Inertia
Acceleration
Time
s 0.323 0.32 0.32 0.387 0.387 0.317 0.317 0.533
*1 Parameters within parentheses are for motor 2.
No.
*1
Name Unit Default
- Drive Model - 4168 4208 4250 4296
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. A5 A6 A7 A8
E2-11
(E4-11)
Motor Rated
Power
kW 75 90 90 110 110 150 150 185
b3-04
V/f Gain
during Speed
Search
% 60 60 60 60 60 60 60 60
b3-06
Speed
Estimation
Current Level
1