Parameter List
11
11.21 Defaults by Drive Model and Duty Rating ND/HD
YASKAWA SIEPC71061705H GA700 Series Technical Manual 617
No.
*1
Name Unit Default
- Drive Model - 4371 4389 4453 4568
C6-01
Normal /
Heavy Duty
Selection
-
HD ND HD ND HD ND HD ND
0 1 0 1 0 1 0 1
o2-04
Drive Model
(KVA)
Selection
Hex. A9 AA AC AD
E2-11
(E4-11)
Motor Rated
Power
kW 185 220 220 260 260 300 300 335
L2-02
Power Loss
Ride Through
Time
s 2 2 2 2 2 2 2 2
L2-03
Minimum
Baseblock
Time
s 1.8 1.9 1.9 2 2 2.1 2.1 2.1
L2-04
Powerloss V/f
Recovery
Ramp Time
s 1 1 1.8 1.8 1.8 2 2 2
L2-05
Undervoltage
Detection Lvl
(Uv1)
- 380 380 380 380 380 380 380 380
L3-24
Motor Accel
Time @ Rated
Torque
s 0.777 0.864 0.864 0.91 0.91 1.392 1.392 1.392
L8-02
Overheat
Alarm Level
°C 125 125 125 125 110 110 125 115
L8-09
Output
Ground Fault
Detection
- 1 1 1 1 1 1 1 1
L8-38
Carrier
Frequency
Reduction
- 2 2 2 2 2 2 2 2
n1-01
Hunting
Prevention
Selection
- 2 2 2 2 2 2 2 2
n1-03
Hunting
Prevention
Time Constant
ms 30 30 100 100 100 100 100 100
n1-16
Hunting
Prevention
High Fc Gain
- 0.50 0.50 0.50 0.50 0.50 0.50 0.50 0.50
n5-02
Motor Inertia
Acceleration
Time
s 0.777 0.864 0.864 0.91 0.91 1.392 1.392 1.392
*1 Parameters within parentheses are for motor 2.
No.
*1
Name Unit Default
- Drive Model - 4675
C6-01
Normal / Heavy Duty
Selection
-
HD1 ND
0 1
o2-04 Drive Model (KVA) Selection Hex. AE
E2-11
(E4-11)
Motor Rated Power kW 315 355
b3-04 V/f Gain during Speed Search % 60 60
b3-06 Speed Estimation Current Level 1 - 0.7 0.7
b3-08 Speed Estimation ACR P Gain - 0.8 0.8
b3-26 Direction Determination Level - 1000 1000
b8-03 Energy Saving Filter Time s 2.00 2.00
b8-04 Energy Saving Coefficient Value - 21.76 23.84
C5-17
(C5-37)
Motor Inertia kgm
2
11.00 12.00
C6-02 Carrier Frequency Selection - 1 7
E2-01
(E4-01)
Motor Rated Current (FLA) A 500 650