Docu ment No. E ZZ024048<1>
Pr epared in October, 2021
10 / 19
7 Troubleshooting
7.5 Minor Faults/Alarms
Underlined text shows additions and modifications.
Cod e
Name
Causes
Possible Solutions
LoG
Com Error /
Abnormal SD card
There is not a micro SD in the
keypad.
Put a micro SD card in the keypad.
The drive is connected to
USB.
The number of log
communication files is more
than 1000.
The micro SD card does not
have available memory
space.
The line number data in a log
communication file is not
correct.
A communication error
between the keypad and
drive occurred during a log
communication.
Set
o5-01 = 0 [Log Start/Stop Selection = OFF]
.
Short-term data logging
st arted while a keypad that
d oes not support short-term
d ata logs was connected.
Connect a keypad that supports short-term data logs.
Not e: The LCD keypad and Bluetooth LCD keypad with
RE V: H or later are supported. The keypad version
REV” is located on the nameplate on the back
of th e keypad.
Se t
o5-00 = 0 [Log Type = Long Term Log]
.
Se t
o5-01 = 0 [Log Start/Stop Selection = OFF]
.
Note: If the drive detects this error, the terminal set to
H2-01 to H2-04
=
6A [MFDO Function Selection = Data
Logger Error]
will activate.

Table of Contents

Related product manuals