282 Upgrade and Maintenance Manual TX300 S7 / RX350 S7
Hard disk drives / solid state drives
7.3.8 Replacing a 3.5-inch HDD module
V CAUTION!
Only remove an HDD / SSD module during operation if the drive is
not currently being accessed. Observe the indicators on the HDD
module, as described in the "PRIMERGY TX300 S7 / RX350 S7
Server" operating manual".
Under no circumstances should you remove an HDD / SSD module
while the system is in operation if you are not sure that the drive is
operated by a RAID controller and belongs to a disk array that is
operating in RAID level 0, 1, 1E, 10, 5, 50, 6 or 60.
An HDD / SSD module can only be replaced during operation in
conjunction with a corresponding RAID configuration.
All HDD / SSD modules (drives) must be uniquely identified so that
they can be reinstalled in their original mounting locations later. If this
is not done, existing data can be lost.
7.3.8.1 Required tools
Preliminary and concluding steps: tool-less
Replacing a 3.5-inch HDD module: tool-less
7.3.8.2 Preliminary steps
Before replacing a 3.5-inch HDD module, perform the following steps:
Ê Locate the defective server as described in section "Locating the defective
server" on page 64.
Ê When working on a tower server, open the HDD bay cover as described in
section "Removing accessible drive and HDD bay covers" on page 91.
Ê Locate the defective HDD module as described in section "Local diagnostic
indicators on the front" on page 67.
Customer Replaceable Units (CRU)
Average task duration: 5 minutes