618 Upgrade and Maintenance Manual TX300 S7 / RX350 S7
Processors
Ê Remove the AC power cords from the PSU cable brackets and disconnect
them from the system as described in section "Disconnecting the server
from the mains" on page 72.
Ê When working on a rack-mounted server, extend it out of the rack as
described in section "Extending the server out of the rack" on page 76.
If further required, remove the server from the rack as described in section
"Removing the server from the rack" on page 77.
Ê Bring the server to its horizontal position.
Ê Open the side / top cover as described in section "Removing the top cover"
on page 79 (rack server) or "Removing the side cover" on page 88 (tower
server).
Ê Remove the air duct as described in section "Removing the system air duct"
on page 100.
Ê Remove the desired processor heat sink as described in section "Removing
processor heat sinks" on page 646.
11.3.3 Removing a processor
I This description applies to the following procedures:
Removing CPU 2 from a dual-processor configuration
Removing CPUs from a defective system board (see section
"Swapping processors" on page 867)
Ê Remove the desired processor heat sink as described in section "Removing
processor heat sinks" on page 646.