EasyManua.ls Logo

Omron F3SG-SRB Series - Standard Muting Mode;Exit-Only Muting Mode with Y-Joint Plug

Omron F3SG-SRB Series
399 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
328
Chapter6 Wiring Examples (for F3SG-SR)
F3SG-SR
User’s Manual
Input/Output Circuit and Applications
6-2-2-2. Standard Muting Mode/Exit-Only Muting Mode with Y-Joint Plug
[Wiring Example]
• When using the Y-Joint Plug/Socket Connector (F39-GCNY2), the following functions are not available.
- External Test
- Operating Range Selection by wiring
- Wired Synchronization
When a functional earth is necessary, wire an earth cable according to the example in
6-2-1-1.
Auto Reset Mode with
Optical Synchronization and EDM Unused. Also refer to
5-4-4.
Functional Earth Connection for more information.
F39-JGR3K-L and
F39-JG
B-L
F39-GCNY2
24 VDC
Wiring for NPN *1
24 VDC
F39-JGR3K-D and
F39-JG
B-D
24V/0V (Brown)
MUTE B (Pink)
MUTE A (Gray)
0V/24V (Blue)
RESET/EDM
(Yellow)
AUX (Red)
OSSD 1 (Black)
OSSD 2 (White)
*5
IN
PLC *2
IN1
IN2
Emitter Reflector
(E39-R1S)
Reflector
B2B1
Reflector Reflector
A2A1
Receiver
Receiver
Emitter
Safety controller
*3 *4
1
PLC: Programmable logic controller (Used for monitoring only. NOT related to safety system.)
A1, A2, B1, B2: Muting sensor (E3Z-R6)
2
1 2
: Indicates a switch position
Function
Setting
DIP switch SD Manager 3
EDM EDM Disabled (factory default setting)
- [External device monitoring] : Disable *6
Interlock Auto Reset (factory default setting)
- [Start interlock] : Disable
[Restart interlock] : Disable *6
Operating Range
Selection
Long (factory default setting) *7
- [Operating Range Selection] : Long mode *6
Standard Muting Mode
When not using the Intelligent Tap or the SD Manager 3, perform wiring according to the wiring diagram.
N/A [Muting] : Enable
[Muting mode] : Standard Muting (Installation
Example1/2) *6
Exit-Only Muting Mode N/A [Muting] : Enable
[Muting mode] : Exit-Only Muting *6
External Test not used N/A
Optical Synchronization Connect the wires according to the diagram above.
Timing chart
MUTEA
MUTEB
OSSD
Unblocked
Blocked
*1. Reverse the polarity of the power supply when using in the NPN system. Select a PLC
and a safety controller of PNP or NPN type according to the system of your application.
*2. When connecting to the PLC, the output mode must be changed with the SD Manager 3
according to your application. Refer to Chapter 4 Setting with SD Manager 3 for more
information on setting this function by the SD Manager 3.
*3. Refer to 6-3. Connectable Safety Control Units for more information.
*4. The safety controller and the F3SG-SR must share the power supply or be connected to
the common terminal of the power supply.
*5. This is the case for a PELV circuit.
*6. When using the Exit-Only Muting, set the function with the SD Manager 3, restore the
settings to the F3SG-SR, and perform wiring according to the wiring diagram.
*7. To set the Short mode, set the function with the DIP Switches on the Intelligent Tap or
the SD Manager 3, restore the settings to the F3SG-SR, and perform wiring according to
the wiring diagram.
Intelligent Tap Needed *6

Table of Contents

Related product manuals