6-2-2-3. Standard Muting Mode/Exit-Only Muting Mode with Intelligent Tap
*1. Reverse the polarity of the power supply when using in the NPN system. Select a
PLC and a safety controller of PNP or NPN type according to the system of your
application.
*2. Also used as OVERRIDE INPUT line.
*3. Make sure to connect an override cancel switch to the RESET line when using the
override function. Otherwise the override state may not be released by the override
cancel switch, resulting in serious injury.
*4. When connecting to the PLC, the output mode must be changed with the SD
Manager 3 according to your application. Refer to Chapter 4 Setting with SD
Manager 3 for more information on setting this function by the SD Manager 3.
*5. Refer to 6-3. Connectable Safety Control Units for more information.
*6. The safety controller and the F3SG-SR must share the power supply or be connected
to the common terminal of the power supply.
*7. For connecting with the IO-Link Master unit, refer to an instruction manual of the
IO-Link Master unit you use.
*8. This is the case for a PELV circuit.
: Indicates a switch position
Function
Setting
DIP switch SD Manager 3
EDM EDM Disabled [External device monitoring] : Disable
Interlock Auto Reset [Start interlock] : Disable
[Restart interlock] : Disable
Operating Range Selection Long [Operating Range Selection] : Long mode
Standard Muting Mode N/A [Muting] : Enable
[Muting mode] : Standard Muting (Installation
Example1/2)
Exit-Only Muting Mode N/A [Muting] : Enable
[Muting mode] : Exit-Only Muting
Test Input N/A
Wired Synchronization Connect the emitter and receiver with the Intelligent Tap.