351
F3SG-SR
User’s Manual
Chapter8 Troubleshooting
Appendix
E
* Factory default setting
8-1-3-4. Interlock Sequence Error Indication
The following table is applied only when the pre-reset function is being enabled.
Blinking: Four times
The F3SG-SR may have been blocked within 0.08 s after muting input A and B were
normally turned ON.
Check that if the muting sensor and the F3SG-SR are installed too close each other.
Check that if the speed of the workpiece is too fast.
Muting may have been released after the F3SG-SR entered the MUTING state but before a
workpiece blocked the F3SG-SR.
Check that the workpiece still remains.
Check that the speed of the workpiece is too slow.
Blinking: Five times
The F3SG-SR entered the MUTING state, but muting may have then been released while a
workpiece passes through the F3SG-SR.
Check that the workpiece still remains.
Check that if the speed of the workpiece is too slow.
Check that the muting sensors have been installed upstream and downstream of the
F3SG-SR with the size of workpieces taken into account. (Using four muting sensors)
Blinking: Six times
Muting may have been released with muting input A and B remained ON after a workpiece
passed through the F3SG-SR.
Check that the workpiece still remains.
Check that the speed of the workpiece is too slow.
Blinking: Seven times
The next muting sequence may have started after muting was released but before the initial
muting condition was established.
Check that if a next workpiece has not entered before the current workpiece passes
through the F3SG-SR.
Check that if the interval between workpieces are too narrow.
SEQ indicator Cause and measures
Blinking: Once
The reset or pre-reset switch may have been pressed before the F3SG-SR receives light.
Check the wiring of the reset and pre-reset signals.
The F3SG-SR may have been blocked or the pre-reset switch may have been pressed
before the pre-reset switch is pressed.
Check the status of the F3SG-SR and the wiring of the pre-reset signal.
Blinking: Twice
After the pre-reset switch was pressed, the pre-reset or reset switch may have been pressed
before the F3SG-SR is blocked.
Check the installation environment of the F3SG-SR.
Blinking: Three times
After the pre-reset switch was pressed and the F3SG-SR was blocked, the pre-reset switch
may have been pressed before the reset switch is pressed.
Check the wiring of the pre-reset signal.
After the pre-reset switch was pressed, a time period from the block of the F3SG-SR to the
press of the reset switch may have exceeded the allowable time.
Check the installation environment of the F3SG-SR as well as pre-reset and reset switches.
The number of blocks of the F3SG-SR may have exceeded the allowable value after the pre-
reset switch was pressed and before the reset switch is pressed.
Check the installation environment of the F3SG-SR.
SEQ indicator Cause and measures