Pulse output instructions
1057
Part III FP Instructions
Stopping pulse output
Pulse output can be stopped by one of the following operations:
Turning the position control trigger to TRUE (pulse output continues until the
target value has been reached and deceleration has completed): The position
control trigger can be started by turning a position control trigger input to TRUE
or by setting bit 6 of the data register storing the pulse output control code from
FALSE to TRUE (e.g. MOVE(16#140, sys_wHscOrPulseControlCode);).
Requesting a decelerated stop: To perform a decelerated stop, set bit 5 of the
data register storing the pulse output control code from FALSE to TRUE (e.g.
MOVE(16#120, sys_wHscOrPulseControlCode);). When a decelerated
stop is requested during acceleration, deceleration is performed with the same
slope as deceleration from the target speed.
Executing an emergency stop: To perform an emergency stop, set bit 3 of the
data register storing the pulse output control code from FALSE to TRUE (e.g.
MOVE(16#108, sys_wHscOrPulseControlCode);).
Note: When stopping, disable all pulse output functions for the channel used in the program.
JOG Operation Type 0
Use the following predefined DUT:
F171_PulseOutput_Jog_Positioning_Type0_DUT
The following parameters can be specified in the DUT:
Control code
Initial and final speed
Target speed
Acceleration time
Deceleration time
Target value
The target speed can be changed during pulse output.
Changing the target speed during pulse output
Without changing the target speed: With changing the target speed:
t
f
1
2
3
45
6
7
8
t
f
1
2
3
45
6
7
8
1
Initial and final speed
5
Deceleration time
2
Target speed
6
Execution condition
3
Target value
7
Position control trigger input
4
Acceleration time
8
Pulse output control flag

Table of Contents

Other manuals for Panasonic FP Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic FP Series and is the answer not in the manual?

Panasonic FP Series Specifications

General IconGeneral
MountingDIN rail
TypePLC
Communication InterfaceRS-232, RS-485, Ethernet (depending on model)
Input Voltage100-240V AC or 24V DC (depending on model)
Output TypeRelay, Transistor
I/O PointsVaries by model
Operating Temperature0°C to 55°C
DimensionsVaries by model
WeightVaries by model

Related product manuals