Timer instructions
334
Part II IEC Instructions
DIV_TIME_REAL
Divide TIME by REAL
To add an enable input and enable output to the instruction, select [With EN/ENO] from the
"Instructions" pane (LD, FBD or IL editor). To reuse an instruction select "Recently used" from the
context menu or press <Ctrl>+<Shift>+<v> in the programming window.
PLC types
Availability of DIV_TIME_REAL (see page 1319)
Data type I/O Function
TIME 1st input dividend
REAL 2nd input divisor
TIME output result
Description
DIV_TIME_REAL divides the value of the first input variable of the data type TIME by the value of
the second input variable of the data type REAL. The REAL value is rounded off to the nearest
whole number. The result is written into the output variable.
Data types
Example
In this example, the same POU header is used for all programming languages. For an example
using IL (instruction list), please refer to the online help.
POU header
All input and output variables used for programming this function have been declared in the POU
header.
Body
The value of variable input_time is divided by the value of the variable input_real. The result is
written in div_result. In this example the input variables have been declared in the POU header.
However, you may enter constants directly at the contact pins of the function.
LD
ST
When programming with structured text, enter the following:
div_result:=DIV_TIME_REAL(input_time, input_real);