Page #1312 background imageLoading...
Page #1312 background image
Appendix Programming Information
1311
Error
code
Name Operation
status
Description and steps to take
E100
to
E199
Stops
E200
to
E299
Self- diagnostic
error set by
F148 (ERR)/
P148 (PERR)
instruction
Continues
The self-diagnostic error specified by the F148 (ERR)/P148
(PERR) instruction is occurred.
Take steps to clear the error condition according to the
specification you chose.
40.9.3 Table of communication check error
Error
code
Name Operation
status
Description and steps to take
E63 PLC error mode
(Available PLC:
FP2/FP2SH/FP3/
FP10SH)
Stops Transfer was attempted in the RUN mode.
Switch the mode and execute once again.
E64 No ROM/RAM error
(Available PLC:
FP2/FP2SH/FP3/
FP10SH)
Stops An abnormality occurred when loading RAM to ROM/IC
memory card. There may be a problem with the ROM or IC
memory card.
-
When loading, the specified contents exceeded the
capacity (256 KB).
-
Write error occurs.
-
ROM or IC memory card is not installed.
-
ROM or IC memory card does not conform to
specifications.
Check the contents of the ROM or IC memory card.
E65 Protect error Stops Transfer was attempted during ROM operation or IC memory
card operation.
Switch the mode and execute once again.
E66 PLC write error
address error
(Available PLC:
FP2/FP2SH/FP3/
FP10SH)
Continues In the programming tool software, program editing is being
attempted by online access, but the program is not in
agreement. (The program disagreement lies in another
block.)Check the program.
E68 Rewrite during RUN
error
(Available PLC:
FP2/FP2SH/FP3/
FP10SH)
Continues When inputting with the programming tool software, editing of
an instruction (ED, SUB, RET, INT, IRET, SSTP, and STPE)
that cannot perform a rewrite during RUN is being attempted.
Nothing is written to the CPU.

Table of Contents

Other manuals for Panasonic FP Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Panasonic FP Series and is the answer not in the manual?

Panasonic FP Series Specifications

General IconGeneral
MountingDIN rail
TypePLC
Communication InterfaceRS-232, RS-485, Ethernet (depending on model)
Input Voltage100-240V AC or 24V DC (depending on model)
Output TypeRelay, Transistor
I/O PointsVaries by model
Operating Temperature0°C to 55°C
DimensionsVaries by model
WeightVaries by model