Analog unit instructions
1099
Part IV Tool Instructions
Input wiring
Voltage input Current input
V0
I0
COM
V1
I1
V2
I2
V3
I3
V4
I4
COM
V5
I5
V6
I6
V7
I7
Input instrument
(ch0)
Input instrument
(ch1)
Input instrument
(ch2)
Input instrument
(ch3)
Input instrument
(ch4)
Input instrument
(ch5)
Input instrument
(ch6)
Input instrument (ch7)
V0
I0
COM
V1
I1
V2
I2
V3
I3
V4
I4
COM
V5
I5
V6
I6
V7
I7
Input instrument
(ch0)
Input instrument
(ch1)
Input instrument
(ch2)
Input instrument
(ch3)
Input instrument
(ch4)
Input instrument
(ch5)
Input instrument (ch6)
Input instrument
(ch7)
Connect input instrument between V and COM terminal. First, connect both V terminal and I terminal. And then
connect input instrument between it and COM terminal.
A/D conversion values
Input current (mA) A/D conversion value
0.0 0
2.5 500
5.0 1000
7.5 1500
10.0 2000
12.5 2500
15.0 3000
17.5 3500
20.0 4000
Processing if the range is exceeded
0mA or less (including
negative value)
0
20mA or more 4000
Input voltage (V) A/D conversion value
0.0 0
0.5 400
1.0 800
1.5 1200
2.0 1600