Data transfer via network
793
Part III FP Instructions
For Relay T/C Register Constant
s1 DWX DWY DWR DWL DSV DEV DDT DLD DFL -
s2, n WX WY WR WL SV EV DT LD FL dec. or hex.
d - WY WR WL SV EV DT LD FL -
No. IEC address Set If
R9007 %MX0.900.7 permanently
R9008 %MX0.900.8 for an instant
the control data s1 exceeds the limit of
specified range
no MEWNET-F master unit is found
the data read exceeds the area of d
Precautions during programming
It is not possible to execute multiple F152_RMRD instructions and F153_RMWT instructions at the
same time.
The program should be set up so that these instructions are executed when the
F152_RMRD/F153_RMWT instruction execution enabled flag (R9035) is on.
R9035 0: Execution inhibited (RMRD/RMWT instruction being executed)
1: Execution enabled
The F152_RMRD instruction only enables a request to be accepted. The actual processing is
carried out at the end of the scan. The F152_RMRD/F153_RMWT instruction completed flag
(R9036) can be used to confirm whether or not the instruction has been executed.
R9036 0: Completed normally
1: Completed with error (The error code is stored in DT9036/DT90036)
DT9036
(DT90036)
If the transmission has been completed with an error (R9036 is on), the contents of the
error (error code) are stored.
Reference: The error codes stored in the DT9036/DT90036
Error code (HEX) Description
16#5B Time-out error (no intelligent unit found at the specified location)
16#68 No memory error (no memory exists at the specified address)
16#71 Send answer time-out error
16#72 Send buffer full time-out error
16#73 Response time-out error
If the error code is 16#71 to 16#73, a communication time-out error has occurred. The time-out
time can be changed within a range of 10.0ms to 81.9s (in units of 10ms), using the setting of
system register 32. The default value is set to 2 seconds.
Operands
Error flags