JUNOS Internet Software Network Operations Guide: Hardware
70 ! Using the Basic Monitoring Method
Temperature The chassis temperature
exceeded 55 degrees C, the
fans turned on to full speed,
and one or more fans failed.
! Check the room
temperature.
! Check the air filter and
replace it.
! Check the air flow.
! Check the fan.
Yellow
The chassis temperature
exceeded 65 degrees, and
the fans turned on to full
speed.
! Check the room
temperature.
! Check the air filter and
replace it.
! Check the air flow.
! Check the fan.
Yellow
The chassis temperature
exceeded 65 degrees C and a
fan failed. If this condition
persists for more than 4
minutes, the router shuts
down.
! Check the room
temperature.
! Check the air filter and
replace it.
! Check the air flow.
! Check the fan.
Red
The chassis temperature
exceeded 75 degrees C. If
this condition persists for
more than 4 minutes, the
router shuts down.
! Check the room
temperature.
! Check the air filter and
replace it.
! Check the air flow.
! Check the fan.
Red
The temperature sensor
failed.