JUNOS Internet Software Network Operations Guide: Hardware
76 ! Using the Basic Monitoring Method
Temperature The chassis temperature has
exceeded 55 degrees C, the
fans have been turned on to
full speed, and one or more
fans have failed.
! Check the room
temperature.
! Check the air filter
and replace it.
! Check the air flow.
! Check the fan.
Yellow
The chassis temperature has
exceeded 65 degrees C and
the fans have been turned on
to full speed.
! Check the room
temperature.
! Check the air filter
and replace it.
! Check the air flow.
! Check the fan.
Yellow
The chassis temperature
exceeded 65 degrees C and a
fan has failed. If this condition
persists for more than 4
minutes, the router shuts
down.
! Check the room
temperature.
! Check the air filter
and replace it.
! Check the air flow.
! Check the fan.
Red
Chassis temperature exceeded
75 degrees C. If this condition
persists for more than 4
minutes, the router shuts
down.
! Check the room
temperature.
! Check the air filter
and replace it.
! Check the air flow.
! Check the fan.
Red
The temperature sensor has
failed.
For technical support,
open a support case
using the Case Manager
link at
http://www.juniper.net
/support/
or call
1-888-314-JTAC (within
the United States) or
1-408-745-9500 (outside
the United States).
Red
Chassis
Component
Alarm Condition Remedy
Alarm
Severity