4.6 Output (Y) Status Setting for Switching STOP to RUN
(1) Output (Y) status setting for changing the status from STOP to RUN
When the C Controller module status is switched from RUN to STOP, the output data
(Y) in the RUN status are saved in the C Controller module and actual outputs are all
turned off.
In the STOP status, the output (Y) status cannot be changed from the user program.
Either of the following two options can be selected for the case of switching STOP to
RUN.
• Outputting the output status data before STOP. (Previous state)
• Clearing the output (Y) data. (Reset output (Y))
(2) Setting applications
When the C Controller module status is changed from STOP to RUN, whether to
resume the previous output or not can be selected in advance.
• When "Previous state" is selected
• When "Reset output (Y)" is selected
Figure 4.6 Timing chart for "Previous state" setting
Figure 4.7 Timing chart for "Reset output (Y)" setting
STOP RUNRUN STOP
Output (Y)
Output (Y)
STOP RUNRUN STOP