5
ACCESS VIA NETWORK MODULES
5.4 CC-Link IE Controller Network Module Access Function
5.4.4 Link device refresh setting
5 - 55
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
FUNCTIONS
5
ACCESS VIA NETWORK
MODULES
6
PREPARATORY
PROCEDURES AND
SETTING
7
I/O NUMBER
ASSIGNMENT
8
MEMORIES AND FILES
(2) Refresh parameters
The refresh parameters are parameters by which data are transferred from the link
devices (LX, LY, LB, and LW) of a CC-Link IE controller network module to the internal
link device buffers (LX, LY, LB and LW buffers) of the C Controller module for use in
the user program.
(a) Link refreshable devices
Up to 64 transfer settings are allowed for each CC-Link IE controller network
module.
The following transfer settings are available.
Transfer the link side device (LX) data to the CPU side device (LX buffer).
Transfer the link side device (LY) data to the CPU side device (LY buffer).
Transfer the link side device (LB) data to the CPU side device (LB buffer).
Transfer the link side device (LW) data to the CPU side device (LW buffer).
(b) Setting refresh parameters
Set refresh parameters in the Refresh parameter settings screen activated from
the <<Parameter settings>> tab of CC IE Control utility.
Figure 5.53 Refresh parameter settings screen