6 - 82
6.10 Initializing/Changing Mode of C Controller Module
6.10.2 Setting the Q06CCPU-V(-B) back to the factory-set status
6
PREPARATORY PROCEDURES AND SETTING
(1) Applications
The C Controller module can be restored by setting it to the initialized status if it does
not operate normally by the following reasons.
Execution of a user program registered to a script file
Unknown IP address or login user set to the C Controller module
Figure 6.55 Operating procedure
Error
Format the standard ROM.
( )
Please consult your local Mitsubishi
service center or representative,
explaining a detailed description of the
problem.
End
No
Yes
No
Yes
Execute the "Default IP setting" mode.
( )
Is the C Controller module
operating normally?
Is the C Controller module
operating normally?
Page 6-84, Section 6.10.2 (3)
Page 6-85, Section 6.10.2 (4)