16
TROUBLESHOOTING
16.5 Hardware Self-Diagnostic Function
16.5.2 Hardware self-diagnostic test and initialization setting of the Q06CCPU-V(-B)
16 - 86
9
DEVICE DESCRIPTION
10
MULTIPLE CPU SYSTEM
OVERVIEW
11
MULTIPLE CPU SYSTEM
CONFIGURATION
12
CONCEPT OF MULTIPLE
CPU SYSTEM
13
COMMUNICATIONS
BETWEEN CPU
MODULES
14
PARAMETERS ADDED
FOR MULTIPLE CPU
SYSTEMS
15
STARTING A MULTIPLE
CPU SYSTEM
16
TROUBLESHOOTING
(3) Selecting a mode in the hardware self-diagnostic mode
(a) Before switching the mode to the hardware self-diagnostic mode
Be sure to perform operations described in Page 16-85, Section 16.5.2 (2).
(b) Switching to the hardware self-diagnostic mode
1) Move the RESET/SELECT switch to the RESET position, and hold the RUN/
STOP/MODE switch at the MODE position.
2) Move the RESET/SELECT switch back to the center.
3) Check that the MODE LED turns on in orange.
Figure 16.28 Switch operation for the hardware self-diagnostics mode (for the Q06CCPU-V)
STOP
MODE RUNI
RESET SEL.
STOP
MODE RUN
RUN
CF CARD
CH2 SD/RD
MODE
On
ERR.
USER
I
RESET SEL.