SYSTEM CONFIGURATION
2.1 System Configuration
2.1.4 System configuration overview
2 - 13
1
OVERVIEW
2
SYSTEM
CONFIGURATION
3
SPECIFICATIONS
4
FUNCTIONS
5
ACCESS VIA NETWORK
MODULES
6
PREPARATORY
PROCEDURES AND
SETTING
7
I/O NUMBER
ASSIGNMENT
8
MEMORIES AND FILES
Precautions
The total extension cable length must be 13.2m (43.31 feet) or less.
Do not install the extension cables together with the main circuit lines (high
voltage and large current).
Set a unique number for each extension base.
The Q6 RB and QA1S6 B extension base units cannot be used.
Connect the extension cable from OUT of the extension cable connector of
the base unit to IN of the next extension base unit.
Mounting 65 or more modules causes an error.
Table 2.3 Restrictions on the system configuration
Maximum number of
extension base units
7 units
Maximum number of I/O
modules
64 modules
Applicable main base
unit model
Q35DB, Q38DB, Q312DB
Applicable extension
base unit model
No power supply module required Q52B, Q55B
Q series power supply module required Q63B, Q65B, Q68B, Q612B
Extension cable model QC05B, QC06B, QC12B, QC30B, QC50B, QC100B
Q series power supply
module model
Q61P-A1, Q61P-A2, Q61P, Q61P-D, Q62P, Q63P, Q64P, Q64PN