EasyManua.ls Logo

Moog MSD Servo Drive Series

Moog MSD Servo Drive Series
320 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Fig. 7.33: Field weakening diagram for synchronous motors
7.7.1Variant1(Table)
Deactivatetable:P 341[0] - CON_FM_ImagSLim=0
P 435[0] - CON_FM_FWMode=(1)Selecttable
Slowlyapproachtheselectedspeeds
Adjustscope:Isdref/SQU2*Imag=%=Fieldweakeningspeed.The
maximumamountofthe"fieldweakening"d-currentisdefinedbyparameter
P 340[0] - CON_FM_Imag(specificationofeffectivevalue).
Enterthevaluesinthetable;P 342[0] - CON_FM_SpeedTab
MOOG
ID
No.: CB40859-001 Date: 02/2018
MSD Servo Drive- Device Help
142
7 Control
7.7.2Variant2(Calc)
When there are very fast speed or load changes in the field weakening range, P435
[0] - CON_FM_FwMode needs to be set to 2. When this is done, a characteristic
curve for a higher control dynamic performance will be calculated.
Features
Veryfastadaptations,withhighdynamism,arepossible(open-loopcontrol
method).
Motorparametersmustbeknownquiteprecisely.
Ifcontinuousoscillationoccurs(voltagelimit)thepresetnegatived-current
valueisthennotsufficient.Scalingparameter
P 436[0] - CON_FW_SpeedScale>100%isusedtoevaluatethemapat
higherspeeds.
The voltage controller is superimposed on the characteristic curve (configuration as
described in variant 1).
The set combination of voltage controller and map entails more commissioning
commitment, but it enables the best stationary behaviour (highest torque relative to
current) and the best dynamic response to be achieved.
Example
The speeds in P342[0] - CON_FM_SpeedTab must continuously increase from
index 0 to 7.

Table of Contents

Related product manuals