Analog unit instructions
1095
Part IV Tool Instructions
Output wiring
Voltage output Current output
V 0
I 0
V 1
I 1
COM
V
I
COM
IN
OUT
Output
instrument
V 0
I 0
V 1
I 1
COM
V
I
COM
IN
OUT
Output
instrument
Connect output instrument between OUT/V and
OUT/COM terminal.
Connect output instrument between OUT/I and
OUT/COM terminal.
D/A conversion values
Value of WY Digital value Analog output
-2000 0 -10 V
0 2047 0 V
Voltage
output (V)
2000 4095 +10 V
0 0 0 mA
2000 2047 10 mA
Current
output (mA)
4000 4095 20 mA
Input variable Data type Function
iIOWordOffset The offset of the first WX/WY address of the RTD unit according
to its position.
FP0R, FP0, FP-Sigma: (use
ExpansionUnitToIOWordOffset_FP0 (see page 1128)) or
unit 1 => addres
s 2, unit 2 => address 4, unit 3 => address 6
FP-X: (use Expa
nsionUnotToIOWordOffset_FPX_FP0 (see page
1129)) or
FP0 adapter address of
unit 1
address of
unit 2
address of
unit 3
1st unit 30 32 34
2nd unit 40 42 44
3rd unit 50 52 54
4th unit 60 62 64
5th unit 70 72 72
6th unit 80 82 84
7th unit 90 92 94
8th unit 100 102 104
iOutChannel
INT
Output value channel
-20002–000->-10V–10V.
0–4000->4mA-20mA
Output variable
iInChannel0–iInChannel1
INT
Input value at corresponding output channel 0–1
0V–5V, 0mA–20mA -> 0–4000.
-10V–10V, -100mV–100mV -> -2000–2000