Analog unit instructions 
 
 
 
 
1104 
Part IV  Tool Instructions 
 
Keep a distance of more than 100mm between the 
input line and the power line/high-voltage line. 
A/D conversion values 
Type 
 
temperature unit °C  temperature unit °F 
range: 
-200.0°C–+500.0°C  -328.0°F–+800.0°F 
resolution: 
0.1 
 
0.1°F   
 
analog input 
value °C 
digital output 
value 
analog input 
value °F 
digital output 
value 
  -200.0 -2000 -328.0 -3280 
 
+500.0 +5000 +800.0 +8000 
 -200.1   -328.1 
 +500.1  +800.1 
if input value 
exceeds the range 
 
RTD broken 
8191 
RTD broken 
8191 
range: 
-80.00°C–+80.00°C  -80.00°F–+80.00°F 
resolution: 
0.01 
 
0.01°F   
 
analog input 
value °C 
digital output 
value 
analog input 
value °F 
digital output 
value 
 
-80.00 -8000 -80.00 -8000 
 
+80.00 +8000 +80.00 +8000 
 -80.01   -80.01 
 +80.01   +80.01 
Pt100 
if input value 
exceeds the range 
 
RTD broken 
8191 
RTD broken 
8191 
range: 
-200.0°C–+300.0°C  -328.0°F–+572.0°F 
resolution: 
0.1 
 
0.1°F   
 
analog input 
value °C 
digital output 
value 
analog input 
value °F 
digital output 
value 
 
-200.0 -2000 -328.0 -3280 
 
+300.0 +3000 +572.0 +5720 
-200.1  -328.0 
 +300.0   +572.0 
if input value 
exceeds the range 
RTD broken 
8191 
RTD broken 
8191 
range: 
-80.00°C–+80.00°C  -80.00°F–+80.00°F 
resolution: 
0.01 
 
0.01°F   
 
analog input 
value °C 
digital output 
value 
analog input 
value °F 
digital output 
value 
 
-80.00 -8000 -80.00 -8000 
 
+80.00 +8000 +80.00 +8000 
 -80.01   -80.01 
 +80.01   +80.01 
Pt1000 
if input value 
exceeds the range 
 
RTD broken 
8191 
RTD broken 
8191 
range: 
-30.0°C–150.0°C  -22.0°F–302.0°F 
resolution: 
0.1 
 
0.1°F   
 
analog input 
value °C 
digital output 
value 
analog input 
value °F 
digital output 
value 
Ni1000 
 
-30.0 -300 -22.0 -220