Analog unit instructions
1116
Part IV Tool Instructions
Keep a distance of more than 100mm between the input line and the
power line/high-voltage line.
A shielded compensating lead wire is recommended.
thermocouple
+
-
A/D conversion values
Type
input temperature
°C
digial value
range:
-100.0°C–500.0°C
-100.0 -1000
+500.0 +5000
-100.1
-1001
+500.1
5001 or 8000
K,J
if input value
exceeds the
range
broken thermocouple 8000
range:
-100.0°C–400.0°C
-100.0 -1000
+400.0 +4000
-100.1
-1001
+400.1
4001 or 8000
T
if input value
exceeds the
range
broken thermocouple 8000
range:
-100.0°C–1500.0°C
0 0
+1500.0 +15000
-0.0
0
+1500.1
15001 or 16000
R
if input value
exceeds the
range
broken thermocouple 16000