Appendix Programming Information
1282
No. Name Default Values
437 Time constant of input X1D
437 Time constant of input X1E
437 Time constant of input X1F
TOOL Port
No. Name Default Values
412 TOOL port - communication mode MEWTOCOL-COM
Slave
MEWTOCOL-COM
Slave/Program
controlled
410 TOOL port - station number 1 1–99
415 TOOL port - baud rate 115200 baud 115200/57600/38400/
19200/9600/4800/240
0 baud
413 TOOL port - sending data length 8 bits 7 bits/8 bits
413 TOOL port - sending parity check With-Odd None/With-Odd/With-
Even
413 TOOL port - sending stop bit 1 bit 1 bit/2 bits
413 TOOL port - sending start code No-STX No-STX/STX
413 TOOL port - sending end code/reception done condition CR CR/CR+LF/ETX/Non
e
420 TOOL port - receive buffer starting address 4096 0–12282 (16k type)
0–32762 (32k type)
421 TOOL port - receive buffer capacity 0 words 0-2048 words
412 TOOL port - modem connection Disable Disable/Enable
COM Port
No. Name Default Values
412 COM port 1 - communication mode MEWTOCOL-COM
Master/Slave
MEWTOCOL-COM
Master/Slave/Progra
m controlled/PLC
Link/Modbus RTU
Master/Slave
410 COM port 1 - station number 1 1–99
415
COM port 1 - baud rate
1)
9600 baud 115200/57600/38400/
19200/9600/4800/240
0 baud
413
COM port 1 - sending data length
1)
8 bits 7 bits/8 bits
413
COM port 1 - sending parity check
1)
With-Odd None/With-Odd/With-
Even
413 COM port 1 - sending stop bit 1 bit 1 bit/2 bits
413
COM port 1 - sending start code
1)
No-STX No-STX/STX
413 COM port 1 - sending end code/reception done
condition
1)
CR CR/CR+LF/ETX/Non
e