Appendix Programming Information
1299
No.
Name Default Values
409 Number of
temperature input
values for averaging
process
0 0–50
If the same input has been set as high-speed counter input, pulse catch
input or interrupt input, the following order of precedence is effective:
High-speed counter Pulse catch Interrupt.
If reset input settings overlap for channel 0 and channel 1, the channel 1
setting takes precedence. If reset input settings overlap for channel 2 and
channel 3, the channel 3 setting takes precedence.
The input modes two-phase, incremental/decremental, or
incremental/decremental control require a second channel. If channel 0 or
channel 2 have been set to one of these modes, the settings for channel 1
and channel 3, respectively, will be invalid.
The settings for pulse catch inputs and interrupt inputs can only be
specified in the system registers.
TOOL Port
No
.
Name Default Values
410 TOOL port - station number 1 1–32
411 TOOL port - modem connection Disable Disable/Enable
411 TOOL port - sending data
length
8 bits 7 bits/8 bits
414 TOOL port - baud rate 19200 baud 19200/9600 baud
COM Port
No. Name Default Values
412 COM port 1 - communication mode MEWTOCOL-CO
M Slave
MEWTOCOL-COM
Slave/Program
controlled/Modbus RTU
Slave
415 COM port 1 -station number 1 1–99
414 COM port 1 - baud rate 9600 baud 19200/9600/4800/2400/12
00/600/300 baud
413 COM port 1 - sending data length 8 bits 7 bits/8 bits
413 COM port 1 -sending parity check With-Odd None/With-Odd/With-Even
413 COM port 1 - sending stop bit 1 bit 1 bit/2 bits
413 COM port 1 - sending start code No-STX No-STX/STX
413 COM port 1 - sending end code/reception done condition CR CR/CR+LF/ETX/None
417 COM port 1- -receive buffer starting address 0 0–1657
418 COM port 1 - receive buffer capacity 0 0-1658
416 COM port 1 - modem connection Disable Disable/Enable