Conversion instructions
645
Part III FP Instructions
under "Recently used" in the pop-up menu. Press <Ctrl>+<Shift>+<v> within the programming
area to open the list of recently used elements.
PLC types
Availability of F78_DA2BIN (see page 1326)
Variable Data type Function
s1 WORD starting 16-bit area for ASCII code (source)
s2 INT specifies number of source data bytes to be converted
d ANY32 area for 32-bit data storage (destination)
For Relay T/C Register Constant
s1 WX WY WR WL SV EV DT LD FL -
s2 WX WY WR WL SV EV DT LD FL dec. or hex.
d - DWY DWR DWL DSV DEV DDT DLD DFL -
No. IEC address Set If
R9007 %MX0.900.7 permanently
R9008 %MX0.900.8 for an instant
the number of bytes specified by s2
exceeds the area specified by s1.
the data specified by s2 is recognized as
"0".
the converted result exceeds the area
specified by d.
the converted result exceeds the 32-bit
area.
ASCII code not corresponding to decimal
numbers (0 to 9) or ASCII characters (+,
-, and SPACE) is specified.
Data types
Operands
Error flags