EM500 Open-Loop Vector Control Inverter User Manual
142
channel selection
2: AI3
3: AI4
4: HDI
5: Communications input
F25.40
Upper Limit water
level analog level
0.0~100.0
%
60.0
F25.41
Lower Limit water
level analog level
0.0~100
%
40.0
F25.42
Water shortage level
analog level
0.0~100.0
%
20.0
F25.43
Non-normal standby
pressure
F25.03~F09.01
%/
MPa
0.1
F25.44
Sewage pool water
level detection
function
0: Disabled
1: Enabled
0
F25.45
Inverter fault
handling
0:All Stop
1: Maintain the status quo.
0
F25.46
Feedback
disconnection
handling
0:All Stop
1: Maintain the status quo.
0
F25.47
Pipe network
overpressure alarm
handling
Ones Place:Overpressure alarm
selection
0: Error
1: Alarm
Tens Place:Switching mode under
overpressure
0: Not Used
1:Scram standby
10
F25.48
~
F25.60
Not Used
F25.61
Primary pump
current running time
0~65535
h
×
F25.62
Primary pump total
running time
0~65535
h
F25.63
Standby pump
current running time
0~65535
h
×
F25.64
Standby pump total
running time
0~65535
h
F25.65
Not Used