EM500 Open-Loop Vector Control Inverter User Manual
178
User must set the parameters of F01.00 - F01.08 as per actual conditions before
motor parameter autotuning and make sure to select a proper type of motor (F01.00=2).
Motor Parameter
Autotuning
0: No Autotuning
1: Stationary Autotuning of
Induction Motor
2: Rotational Autotuning of
Induction Motor
11: Stationary Autotuning
of Synchronous Motor
12: Rotational Autotuning
of Synchronous Motor
F01.34=0: No Autotuning
F01.34=1: The induction motor remains stationary in parameter autotuning.
User must set motor type (F01.00) and motor nameplate parameters (F01.01 -
F01.08) correctly before the stationary autotuning of induction motor. By stationary
autotuning, user may get relevant parameters of induction motor, including F01.09 -
F01.13.
This method mainly applies to the working condition where motor can not rotate,
but its effect is not as good as that of rotational autotuning.
F01.34=2: The induction motor remains rotational in the parameter autotuning.
User must set motor type (F01.00) and motor nameplate parameters (F01.01 -
F01.08) correctly before rotational autotuning of induction motor. By rotational
autotuning, user may get relevant parameters of induction motor, including F01.09 -
F01.13.
This method mainly applies to the working condition where motor can rotate, but
better not to have a load or better to have a light load in parameter autotuning; otherwise
the autotuning effect will go down.
F01.34=11: Synchronous motor remains stationary in parameter autotuning.
User must set motor type (F01.00) and motor nameplate parameters (F01.01 -
F01.05) correctly before the stationary autotuning of the synchronous motor. By