EM500 Open-Loop Vector Control Inverter User Manual
347
disruptions
Detection of
filtering time
This code is used to set the filter time for material supply disruptions detection, effective
for both automatic detection and external detection.
No.
Function
Range
Unit
Default
Type
F27.36
The current
feedforward gain
value
-500.0~500.0
%
XXX
×
This code is used to check the current feedforward gain
7.24 F28 Air Compressor Application
No.
Function
Range
Unit
Default
Type
F28.00
Application macro
0: Application of air compressor
all-in-one macros
0
By manually resetting the factory settings, the parameters of the inverter will be restored
to the parameters special for the compressor
No
explain
0: Application of air compressor
all-in-one macros
Set F 16.00 = 2, and select the macro, restore factory settings. The application parameters
are automatically set to the following defaulted values
The basic parameters (motor parameters need to be set manually, and make static
autotuning for the motor parameters)
F00.02
Command Source Options
2: Communication Control
F00.05
Auxiliary Frequency Source B
Options
10Air compressor integrated
PID
F00.06
Frequency Source Options
1: Auxiliary Frequency Source
B
F00.17
Upper Limit Frequency Control
Options
200.00Hz
F00.18
Upper Limit Frequency
200.00Hz
F00.23
Carrier Frequency
4.0k