EM500 Open-Loop Vector Control Inverter User Manual
97
6: Communication Percentage Setting
Note: Motor Rated Voltage is 100%
F05.08
Numeric Setting of
VF Separation
Voltage
0.0 - 100.0 (100.0= Motor Rated
Voltage)
%
0.0
F05.09
Rise Time of VF
Separation Voltage
0.00 - 60.00
s
2.00
F05.10
V/F Stator Voltage
Drop Compensation
Gain
0.00 - 200.00
%
100.00
F05.11
V/F Slip
Compensation Gain
0.00 - 200.00
%
100.00
F05.12
V/F Slip Filter Time
0.00 - 10.00
s
1.00
F05.13
Oscillation
Suppression Gain
0 - 20000
100
F05.14
Oscillation
Suppression End
Frequency
0.00 - 600.00
Hz
55.00
F05.15
Sagging Control
Frequency
0.00 - 10.00
Hz
0.00
F05.16
Energy Saving Rate
0.00 - 50.00
%
0.00
F05.17
Energy Saving
Actuation Time
1.00 - 60.00
s
5.00
F05.18
Compensation Gain
of Magnetic Flux of
Synchronous Motor
0.00 - 500.00
%
100.00
F05.19
Filter Time Constant
of Magnetic Flux
Compensation of
Synchronous Motor
0.00 - 10.00
s
0.50
F06
Vector Control Parameter Group
F06.00
Speed Proportional
Gain ASR_P1
0.00 - 100.00
12.00
F06.01
Speed Integral Time
Constant ASR_T1
0.000 - 30.000
0.000: No Integral
s
0.200
F06.02
Speed Proportional
Gain ASR_P2
0.00 - 100.00
8.00
F06.03
Speed Integral Time
Constant ASR_T2
0.000 - 30.000
0.000: No Integral
s
0.300
F06.04
Switching
0.00 - Switching Frequency 2
Hz
5.00