2.3 Considerations for Installation Site
Caution
3 When carrying and transporting inverter, please hold its bottom.
Only taking the face panel would result in the risk of hitting your foot due to its
dropping.
4 Please install inverter onto a metal panel or other non-flammable material
panel.
Installing it onto flammable materials may result in fire risk.
5 When at least two inverters are installed in the same control cabinet, please set a
cooling fan and maintain the air temperature of air inlet below 40.
Overheating would result in a fire or other accidents.
Installation Site
The installation site shall have the following conditions:
1. Well-ventilated indoor place.
2. Ambient temperature: -10
- 40
.
3. Avoid high temperature and high moisture, humidity < 90%RH, no water drops
or any other condensation.
4. Do not install inverter onto wood or other flammable materials.
5. No direct sunlight.
6. No flammable or corrosive gas or liquid.
7. No dust, oily dust or floating fiber or metal particles.
8. Installation base shall be solid and free from vibration.
9. No electromagnetic interference and away from interference source.
Ambient Temperature
For reliability purpose, please install inverter at a well-ventilated place. A cooling
fan or an air-conditioner shall be installed and the ambient temperature shall be kept
below 40
, when inverter is installed in a closed box.