EM500 Open-Loop Vector Control Inverter User Manual
164
F00.06=2: Main and Auxiliary Arithmetic Results
Final setting frequency is determined through main and auxiliary arithmetic results
(refer to F00.08).
F00.06=3: Switching between Main Frequency Source A and Auxiliary
Frequency Source B
Final setting frequency is determined through input function “26: Frequency Source
Switching”. If the input function is disabled, final setting frequency is determined by
main frequency source A; if the input function is enabled, final setting frequency is
determined by auxiliary frequency source B.
F00.06=4: Switching between Main Frequency Source A and Main & Auxiliary
Arithmetic Results
Final setting frequency is determined through input function “26: Frequency Source
Switching”. If the input function is disabled, final setting frequency is determined by
main frequency source A; if the input function is enabled, final setting frequency is
determined by main and auxiliary arithmetic results. See F00.08 for details.
F00.06=5: Switching between Auxiliary Frequency Source B and Main &
Auxiliary Arithmetic Results
Final setting frequency is determined through input function “26: Frequency Source
Switching”. If the input function is disabled, final setting frequency is determined by
auxiliary frequency source B; if the input function is enabled, final setting frequency is
determined by main and auxiliary arithmetic results. See F00.08 for details
0.00 Hz - Maximum
Frequency
F00.07 is used to set the numeric frequency, with its maximum value limited by the
maximum frequency (F00.16)
0: Main Frequency Source
A + Auxiliary Frequency