EasyManua.ls Logo

Sinee EM500 - Start;Stop Control Parameter Group

Sinee EM500
459 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EM500 Open-Loop Vector Control Inverter User Manual
94
Pulse Output
F03.26
Filter Time of Y2
High-Frequency
Pulse Output
0.00 - 10.00
s
0.10
F03.27
M1 Output Offset
-100.0 - 100.0
%
0.0
F03.28
M1 Output Gain
-10.00 - 10.00
1.00
F03.29
M2 Output Offset
-100.0 - 100.0
%
0.0
F03.30
M2 Output Gain
-10.00 - 10.00
1.00
F04
Start/Stop Control Parameter Group
F04.00
Start Mode
0: Start Directly
1: Rotation Speed Tracking Start
0
F04.01
Start Frequency
0.00 - 10.00
Hz
0.00
F04.02
Start Frequency
Retention Time
0.00 - 60.00, Disabled at 0.00
s
0.00
F04.03
DC Brake Current at
Start
0.0 - 100.0 (100.0= Motor Rated
Frequency)
%
100.0
F04.04
DC Brake Time at
Start
0.00 - 30.00
s
0.00
F04.05
Not Used
F04.06
Pre-Excitation
Current
50.0 - 500.0 (100.0=Idling Current)
%
100.0
F04.07
Pre-Excitation Time
0.00 - 10.00
s
0.10
F04.08
Rotation Speed
Tracking Method
0: Start from Maximum Frequency
1: Start from Stop Frequency
2: Start from Power frequency
0
F04.09
Rise Time of
Rotation Speed
Tracking Voltage
0.05 - 10.00
s
0.30
F04.10
Deceleration Time
of Rotation Speed
Tracking
0.1 - 20.0
s
2.0
F04.11
Rotation Speed
Tracking Current
30.0 - 150.0 (100.0=Inverter Rated
Current)
%
60.0
F04.12
Rotation Speed
Tracking
Compensation Gain
1.00 - 1.30
1.05
F04.13
Not Used
F04.14
Acceleration/Decele
ration Mode
0: Linear Acceleration/Deceleration
1: S Curve Acceleration/Deceleration
0

Table of Contents